[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm. The alkalinity was 30 ppm.
Raise the total alkalinity to at least 60 ppm. Correct By: 05-Jul-2021


Inspection Information


Facility Type: Spa

[?] Inspection Type: Standard

Inspection Date: 25-June-2021


Comments
Ensure the noted finding is correct before next routine inspection. Otherwise, the spa was in good operating order at time of inspection.