3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The chlorine was at 0 ppm at time of inspection. Note: Waiting on chlorine delivery. Correct before opeining pool.
Minimum disinfection residual shall be maintained as required. Correct By: 05-Jun-2018
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Deck warning signs were not maintained in a clearly legible/visible manner. The 'No Life Guard On Duty" warning signs were faded. Note: Replace signs.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. Correct By: 08-Jun-2018
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The gate was not self closing. Please repair before opening.
Correct By: 05-Jun-2018
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
The reagents to test pool water was expired. Note: Waiting on new ones from supplier.
Correct By: 08-Jun-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 05-June-2018
Comments |
---|
Ensure noted violations are corrected before opening pool and approved to operate this season. Note: Handed operator pool license for season. (Waiting on chlorine delivery, new signs, and reagents) |