[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (D)(8)(c) / Test kit reagents fresh/ properly stored.
Test kit reagents were not fresh or stored properly. All reagents in pool kit were beyond expired.
Obtain fresh reagents and store them properly. Correct By: 15-Aug-2023


Inspection Information


Facility Type: Pool

[?] Inspection Type: Follow-up

Inspection Date: 06-September-2023

The following violation(s) have been corrected since the last inspection.
3701-31-04 ( D )(6)(a)/ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low. Correct By: 15-Aug-2023
3701-31-04 (D)(02)/Public swimming pool is continuously disinfected using a chemical feeding device connected to the circulation system
The pool was not being continuously disinfected using a chemical feeding device connected to the circulation system
Repair or replace the disinfection system so that the pool is continuously being disinfected. Correct By: 15-Aug-2023
3701-31-04(D)(6)(a)(2)/Pool free chlorine disinfectant residual shall be above 1 ppm.
Pool free chlorine disinfectant residual was below 1 ppm.
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. Correct By: 05-Sep-2023
Comments
Pool chemicals and ORP have been corrected and service came out to repair parts.