[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Flow gauge was stuck at bottom position.
Please have the gauge serviced.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 08-August-2023

Comments
Flow gauge was stuck at bottom position, please have the gauge serviced. ORP was below required minimum, please adjust pool chemistry accordingly or have the chemical controller inspected to determine the issue. No other violations noted at time of inspection. KJS