[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. ORP reading at 620 mv.
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant. Ladder entering baby pool is loose and needs tightened.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm. Alkalinity recorded at 50 ppm.
Raise the total alkalinity to at least 60 ppm.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 29-June-2023

Comments
ORP and alkalinity are low. Please tighten the ladder for the wading (baby) pool.