[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Corrected During Inspection Required flow meter gauge was not functional while the pool is in operation. The PIC had maintenance correct immediately.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. The pH was 7.0 ppm.
Treat the pool water so that the pH is within the acceptable range. Correct By: 29-Jun-2018
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm. The total alkalinity was 40 ppm.
Raise the total alkalinity to at least 60 ppm. Correct By: 29-Jun-2018


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 24-May-2018

Comments
Ensure noted findings are corrected before opening. The flow meter was stuck. Otherwise, the majority of the water chemistry was within required parameters; approved to operate this season. Note: Handed operator pool license for season.