3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Corrected During Inspection Chlorine disinfectant residual was less than 1 ppm for the pool. 0 ppm chlorine in the pool. Corrected. Chorine was raised to 3 ppm during the inspection.
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Repeat Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection. Automatic Chemical controller is nut functioning causing there to be no chlorine in the pool. Automatic Chemcial Controller was bypassed during the inspection.
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Disinfection residuals were not tested daily at pool side and/or at the required intervals for pools/automatic chemical controllers/special features. Automatic Chemical controller not functioning properly and readings are not being taken more than once per day. You must take readings every 4 hours the pool is in operation until the automatic chemical controller is replaced.
Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. If an ACC is in use the disinfectant residual must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the disinfectant residual must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
pH was not tested daily at pool side and/or at required intervals for pools/automatic chemical controllers/special features. ACC is broken and readings are only being taken once per day. Must take readings every 4 hours until the ACC unit is replaced.
pH must be tested prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use pH must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the pH must be tested at 1 special feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat Corrected During Inspection pH was outside the range of 7.2 to 7.8. pH was 7.0. Corrected. pH was raised to 7.6 during the inspection.
Treat the pool water so that the pH is within the acceptable range.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 15-June-2018
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(2)/Authorized representative is on-site or within 30 minutes of pool location Authorized representative was not on-site or within 30 minutes of pool location. Authorized representative responded within 40 minutes. Make arrangements to have an authorized representative available while pool is in operation. |
Comments |
---|
Automatic chemical controller is not properly functioning. Chemical (Chlorine and pH) readings must be taken every 4 hours during operation of the pool until the automatic chemical controller is replaced. A follow up inspection will be conducted on 6-18-18 to ensure that either the automatic chemical controller has been replace or chemical readings are being taken and recorded every 4 hours. |