3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Chlorine observed at 0.5ppm. Ensure a minimum of 1ppm of chlorine prior to opening and when in use.
Minimum disinfection residual shall be maintained as required. Correct By: 01-Jun-2022
3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
Deck surfaces observed concrete lining and deck surface in need of repair.
Repair areas of the concrete deck where concrete is breaking apart. Correct By: 01-Jun-2022
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were observed faded, not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. Correct By: 01-Jun-2022
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Perimeter barrier gate to wading pool observed to not self close.Ensure self closing gate and latch.
Ensure self closing gate and latch. Correct By: 01-Jun-2022
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. pH observed at 7.0.
Treat the pool water so that the pH is within the acceptable range. Correct By: 01-Jun-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 20-May-2022
Comments |
---|
Ensure all noted findings are corrected prior to opening. Gave license to operator on site. |