3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. Observed ORP at 510mv
Have the ACC unit inspected to determined why the ORP is low. Correct By: 01-Jul-2022
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
The flow meter was observed to be stuck. Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation. Correct By: 01-Jul-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 15-June-2022
Comments |
---|
ORP reading low. Flow meter stuck, unable to get reading. Water chemistry within required parameters. Ensure all noted findings are corrected prior to next inspection. |