3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8. Observed at 6.5
Treat the pool water so that the pH is within the acceptable range. Correct By: 15-Jul-2023
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm. Observed at 30ppm
Raise the total alkalinity to at least 60 ppm. Correct By: 15-Jul-2023
3701-31-04 (C)(6) / Pool water temperature does not exceed 90 degrees Fahrenheit without approval from the Director
Pool water temperature was above 90 degrees Fahrenheit without approval from the Director of Health. Observed at 93 degress Farenheit.
Either reduce the water temperature of the pool to below 90 degress Fahrenheit or seek approval to operate at a higher temperature from the Director of Health. Correct By: 15-Jul-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 14-July-2023
Comments |
---|
Observed low alkalinity, low pH and a high water temperature. Other water quality parameters were within the required ranges at the time of inspection. |