[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.


Inspection Information


Facility Type: Spa

[?] Inspection Type: Standard

Inspection Date: 11-January-2016