3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv. The ORP reading was 636 mv.
Have the ACC unit inspected to determined why the ORP is low. Correct By: 31-Mar-2022
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8. The pH was 8.0.
Treat the pool water so that the pH is within the acceptable range. Correct By: 31-Mar-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 28-February-2022
Comments |
---|
Ensure noted findings are corrected before next routine inspection. Otherwise, all other water parameters were within requirements and reports were readily available at time of inspection. Good job! |