[?] A summary of the violations found during the inspection are listed below.

No critical violations were documented at the time of inspection.

No violations were documented at the time of inspection.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Follow-up

Inspection Date: 01-November-2022

The following violation(s) have been corrected since the last inspection.
3701-31-04 (B)(4)(a)(i)/Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Disinfection residuals were not tested daily at pool side or at the required intervals for the pool when the automatic chemical controller was not functioning properly. The operator was only testing once a day and not testing the water every 4 hours as required when the ACC is not working properly. Furthermore, the weekend readings were missing all together. Note: Ensure the employee is testing at required time frame until the ACC is repaired and make certain the weekends are recorded as well.
Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. If an ACC is in use the disinfectant residual must be tested every 12 hours while the pool is in use. Correct By: 30-Nov-2022
3701-31-04 (B)(4)(a)(iv)/Water temperatures are recorded daily
Water temperatures were not being recorded daily. Ensure the water temperatures are recorded daily. Note: Wrote example on report and circled example.
Take and record the water temperature at least once/day. Correct By: 31-Oct-2022
3701-31-04 (B)(4)(a)(vi)/Total alkalinity is tested weekly
Total alkalinity was not tested weekly. The total alkalinity was not tested. Took photos of several reports that proved this was not being completed. Photos on hand. Note: Ensure alkalinity is tested and recorded weekly.
Test total alkalinity at least once/week. Correct By: 30-Nov-2022
3701-31-04 (C)(2)/pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. The pH was 8.0. Ensure this is corrected before next routine inspection.
Treat the pool water so that the pH is within the acceptable range. Correct By: 30-Nov-2022
Comments
We appreciate you prompt response regarding correcting the findings. The sign was removed and all water parameters were within requirements at time of inspection. New inspection records were filled out and available for review. Good job!