[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps. Was unable to locate a flow meter on pool equipment.
Properly install a flow meter or have a pump curve available for every water pump used for the pool. Correct By: 21-Jun-2023
3701-31-04 (D)(7)(b) / pH and ORP values shall be displayed.
Critical ORP value was not displayed on the ACC unit
Have the ACC unit serviced or replaced so that the ORP value is displayed Correct By: 21-Jun-2023


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 20-June-2023

Comments
No flow meter present, unable to obtain ORP reading at the time of inspection. All other parameters were in the required ranges at the time of inspection. Need to ensure ACC is operating properly and that a flow meter is present.