[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Repeat Combined chlorine was not tested daily at pool side prior to use.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.


Inspection Information


Facility Type: Special Use

[?] Inspection Type: Standard

Inspection Date: 24-July-2018