[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Corrected During Inspection ORP reading was below 650 mv. Observed at 635 mV.
Have the ACC unit inspected to determined why the ORP is low. Correct By: 18-Jul-2023
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat Corrected During Inspection pH was outside the range of 7.2 to 7.8. Observed at 8.0
Treat the pool water so that the pH is within the acceptable range. Correct By: 18-Jul-2023


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 17-July-2023

Comments
pH observed to be high, ORP observed to be low. Pool operator was on site at the time of these findings and immediately initiated corrections. All other water quality parameters were within the required ranges at this time.