3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8. The pH was 7.0 ppm.
Treat the pool water so that the pH is within the acceptable range. Correct By: 31-Dec-2019
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm. The total alkalinity was 40 ppm.
Raise the total alkalinity to at least 60 ppm. Correct By: 31-Dec-2019
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 28-November-2019
Comments |
---|
Ensure the noted violations are corrected before next inspection. |