3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Chlorine disinfectant residual was less than 1 ppm for the pool. Corrected. Chorine was raised to 3 ppm during the inspection.
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 28-June-2017
Comments |
---|
Chemical controller was in lockout mode when I arrived at the facility. Chemical pumps were not operating due to lockout mode. Pool operator responded within 30 minutes and reset the system. Chlorine was raised to 3 ppm by the end of the inspection. |