3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(1)(g) / Water clarity shall be sufficient to see the pool bottom (or Secchi disc).
Critical Water clarity was not sufficient to see the pool bottom (or Secchi disc)
Do not operate the pool when water clarity is poor.
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records.
All facility records must be maintained and available for review upon request.
3701-31-04 (B)(4)(a)(i) / Disinfection residuals are tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
Disinfection residuals were not tested daily at pool side and/or at the required intervals for pools/automatic chemical controllers/special features.
Test the disinfection residual every day before bathers enter the water. Disinfection residual must then be tested every 4 hours when an ACC is not in use. If an ACC is in use the disinfectant residual must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the disinfectant residual must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine was not tested daily at pool side prior to use.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(4)(a)(iii) / pH is tested daily at pool side at required intervals for pools/automatic chemical controllers/special features
pH was not tested daily at pool side and/or at required intervals for pools/automatic chemical controllers/special features.
pH must be tested prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use pH must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the pH must be tested at 1 special feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
3701-31-04 (B)(4)(a)(v) / Water clarity are not present
Water clarity was not sufficient to see the pool bottom (or Secchi disc).
Do not operate the pool while the water is unclear. Determine cause of the lack of clarity and immediately correct the issue prior to bathers using the public swimming pool.
3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
Repeat Deck surfaces had standing water or other hazards. The skimmer's plastic cover was cracked and posed a tripping hazard. Replace the broken skimmer lid to reduce the likelihood of accidents on the pool deck.
Repair areas of the deck where standing water is occuring. If more than 50% of the deck must be replaced, plans must be submitted to the Ohio Department of Health for review and approval.
3701-31-04(D)(6)(a)(1) / Combined chlorine shall not exceed 1.0 ppm.
Combined chlorine was greater than 1.0 ppm.
Treat the pool so that the combined chlorine is less than 1 ppm.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 04-March-2024