[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. The ORP was 625.
Have the ACC unit inspected to determined why the ORP is low. Correct By: 30-Jul-2021
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not recording operational readings for the weekends. The records are missing daily readings for numerous Saturday and Sunday intervals. The PIC stated, "they will train someone to check weekend readings."
All facility records must be maintained and available for review upon request. Correct By: 30-Jul-2021


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 30-June-2021

Comments
Ensure noted findings are corrected before next routine inspection. Otherwise, the water parameters recorded met requirement at time of inspection.